A cube result is not a verdict until it clears two gates: the mean of its group of four, and its own individual floor. Here is how IS 456:2000 applies them, with a worked M25 decision.

Aug 30, 2026 | 12 min read | Last reviewed: 30 Aug 2026
M25 · FOUR SAMPLES IS 456:2000 TABLE 11 (AMENDMENT 4) fck − 3 = 22.0 group gate = 28.5 (fck + 0.825σ) S1 S2 S3 S4 group mean 29.95 ✓ CONFORMS IS 456:2000 Cl 16.1 & 16.3 · Table 11 · Table 8 σ

Codes & standards referenced

IS 456:2000Cl 15.2 / 15.2.2 sampling · Cl 16.1 & 16.3 acceptance · Cl 16.4 non-conformity · Cl 17 investigation
IS 516Cube specimen preparation and compressive strength testing
IS 1199 (Part 1):2018Fresh concrete sampling practice

From fresh concrete to a verdict

The acceptance logic sits at the end of a chain, and every link has to hold. Sampling follows IS 456 Cl 15.2 with fresh-concrete practice per IS 1199 (Part 1):2018. Each sample is a set of three 150 mm cubes cast and tested per IS 516, and the sample result is the average of those three cubes. The register then forms groups of four non-overlapping consecutive sample results — samples 1–4, 5–8, 9–12 — in sampling order. No cherry-picking, no sliding a weak result into the next group.

Concrete quantity per grade Minimum samples (Cl 15.2.2)
1–5 m³1
6–15 m³2
16–30 m³3
31–50 m³4
Above 50 m³4 plus 1 for each additional 50 m³ or part thereof

Reference: IS 456:2000 Cl 15.2.2. One sample = three cubes; the sample result is their average.

Which σ applies

The mean gate needs a standard deviation. Until the site establishes one from at least 30 results, use the assumed values of Table 8: 3.5 N/mm² for M10–M15, 4.0 N/mm² for M20–M25, and 5.0 N/mm² for M30 and above. The assumed σ is a stand-in, not a right — start building the project data set from the first pour, and switch to the established value as soon as it exists. A tighter established σ raises the bar your group means must clear; a looser one lowers it. Either way the arithmetic stays honest.

The two gates of Table 11

Gate 1, the group mean: the mean of each group of four must equal or exceed the greater of fck + 0.825σ — rounded off to the nearest 0.5 N/mm² — and fck + 3. Gate 2, the individual floor: every single sample result must be at least fck − 3. A brilliant group mean cannot rescue a single failing result, and one strong result cannot rescue a failing group.

Grade (assumed σ) fck + 0.825σ, rounded to 0.5 fck + 3 Governing group gate Individual floor
M15 (3.5)17.9 → 18.01818.012
M20 (4.0)23.3 → 23.52323.517
M25 (4.0)28.3 → 28.52828.522
M30 (5.0)34.1 → 34.03334.027
M40 (5.0)44.1 → 44.04344.037

Reference: IS 456:2000 Table 11 as amended through Amendment 4; assumed σ per Table 8.

A worked M25 verdict

Four samples from an M25 pour, tested at 28 days, with each sample result already the average of its three cubes. Assumed σ = 4.0 N/mm².

Sample Result (mean of 3 cubes), N/mm² vs floor fck − 3 = 22
129.6PASS
230.4PASS
328.6PASS
431.2PASS

Now the instructive near-miss. Suppose the four results had been 28.4, 26.9, 31.2 and 25.8. The group mean is (28.4 + 26.9 + 31.2 + 25.8) / 4 = 28.075. That clears fck + 3 = 28 — and it still fails, because the governing gate is 28.5. Every individual result clears 22 comfortably, but the mean gate does not care. The group is non-conforming, and the concrete it represents goes down the Cl 16.4 investigation route.

Small pours: a different regime

Table 11's Note 2 handles pours up to 30 m³ where the Cl 15.2.2 frequency yields fewer than four samples. There, the mean of all available sample results must reach fck + 4, each individual result must be at least fck − 2, and if only one sample is taken, that single result must reach fck + 4 on its own. For our M25 example, an 18 m³ pour calls for three samples: their mean must be ≥ 29 N/mm² and each result ≥ 23 N/mm². The higher bar is the price of judging a small data set — with few results, a group mean cannot smooth out one bad batch, so each pour carries more of its own proof.

When a group fails

A failed group does not authorise demolition or silent retesting. Cl 16.3 ties each group to the limited quantity of concrete it represents (a group represents a limited quantity — up to 60 m³). Cl 16.4 then routes the affected concrete to structural investigation: the engineer assesses the actual member, typically with non-destructive testing or cores under Cl 17. Under Cl 17.4.3, core results support acceptance when the average equivalent cube strength is at least 85% of fck and no single core falls below 75% of fck. Quarantine the records first: batch tickets, sampling identity, curing and machine calibration. Half of "failed" groups trace back to testing practice, not to concrete — and you cannot tell which half without the paperwork.

Check your register

New to the vocabulary of characteristic strength and σ? Part 5 of our glossary covers the testing terms, and the design side of the story — why the target mean sits at fck + 1.65σ — is in the IS 10262:2019 walkthrough.

Related articles

AH
About the author

Amit Haridas

Founder & Proprietor, ConcreteInfo. 25+ years of experience in concrete technology, RMC plant operations, construction quality, consulting and technical training across India.

Indicative tool — not a substitute for engineering judgement. Results are computed from formulae and reference values cited to Indian Standards and other published codes as named on this page, using nominal default assumptions; clause and table references are given in good faith for study and preliminary checks. Always verify the current edition and amendments of any cited standard in the BIS catalogue before relying on it. Final mix proportions, structural checks and construction decisions must be confirmed by a qualified engineer against the project design brief, drawings and site conditions. ConcreteInfo accepts no liability for design, procurement or construction decisions taken on the basis of these tools. Code references & rights: Indian Standards are the property of the Bureau of Indian Standards (© BIS) — official PDFs at bis.gov.in. Shared in good faith as technical reference for the civil engineering fraternity — always verify against the official publication.